Case Study · Real Estate Transactions·Erie, PA · 2025

Commercial blower-door diagnostics identify $4,200/year heating-loss retrofit, Erie PA

An Erie PA commercial property manager retained building-performance diagnostics on a 1968-construction office building. Blower-door + thermal imaging + duct-blaster testing identified envelope and duct leakage paths that explained chronic comfort complaints + high heating costs.

Building age1968
Pre-retrofit ACH11.4
Post-retrofit ACH5.8
Annual savings$4,200

§

Context

A 14,000 sq ft 1968-construction Erie PA commercial office building (3 stories) with chronic occupant comfort complaints (cold corner offices in winter, hot south-facing offices in summer) and unusually-high natural gas heating costs ($14,000-$16,000 annually). The property manager engaged us for envelope and HVAC diagnostics as the first step before deciding on a retrofit scope and budget.

§

Methodology

Pre-test combustion-safety check on the building's gas-fired hot-water boilers (CO2 stack analysis, manometer differential testing). Blower-door whole-building depressurization test using a Minneapolis BlowerDoor system, depressurizing to -50 Pa for measurement. Duct-blaster test on the air-handler system. Thermal imaging (FLIR T620) of the building envelope during depressurization at -25 Pa to identify leakage paths. PFT (perfluorocarbon tracer) measurements at 5 occupant zones to quantify air exchange rate per zone.

§

Test findings

Whole-building leakage: 11.4 ACH50 (air changes per hour at 50 Pa). Significantly higher than the 6-8 ACH50 target for commercial buildings of this era and orientation. Thermal imaging during depressurization identified specific leakage paths: 3 disused chimney penetrations in the upper floor not properly sealed; major air-leakage at the original (1968) window frame perimeters on the east and west facades; uninsulated rim-joist gaps on the basement perimeter; duct system leakage at the basement plenum estimated at 22% of supply air volume per duct-blaster test.

§

Recommended retrofit

Detailed engineering report identified prioritized retrofit scope: chimney sealing + insulation ($2,800); rim-joist spray foam ($4,400); duct plenum sealing with mastic + UL-181 tape ($1,800); window-frame caulking + weatherstripping ($3,200); estimated total retrofit cost $12,200. Modeled energy savings: $4,200 per year heating + $800 per year cooling, payback period 2.4 years. Modeled post-retrofit ACH50: 5.8 (within commercial target range).

§

Implementation + verification

Property manager implemented the retrofit over 4 months with weatherization contractors selected from our recommended-contractor list. We returned 6 weeks after retrofit completion for verification blower-door + duct-blaster testing. Measured post-retrofit ACH50: 5.8 (matching the engineering target). Duct leakage reduced to 6% of supply air volume.

Outcome

First full heating season post-retrofit: natural gas costs dropped to $9,400 from the prior $14,200 average. Actual savings $4,800 in Year 1, slightly exceeding the modeled $4,200. Occupant comfort complaints in the previously-cold corner offices resolved. Payback period on the $12,200 retrofit is on track for 2.3 years actual vs 2.4 years modeled.

— — Takeaway

Commercial building diagnostics with blower-door + thermal imaging + duct-blaster testing produces engineering-grade retrofit scopes that pay back within 2-4 years on most 1960s-1980s-construction Erie PA buildings. The diagnostic engagement is the highest-ROI first step before committing to retrofit capital. Property managers consistently underestimate the savings opportunity without the diagnostic data.

Related

More case studies

Same protocol applied across different scenarios. Browse the full archive or explore the real estate transactions hub.

Schedule · 48hr appointment

Unsure about your air? Schedule a test.

48-hour appointment window. 24-hour lab turnaround. Licensed inspectors, unmarked vehicles, statewide coverage in NY and PA.